Roof Construction

EXAMPLES OF IMPROPER CONSTRUCTION

Below are some image galleries where I reflect roofing and construction work from other contractors where clear issues are highlighted.

SIDEWALL FLASHING NOT PROPERLY INSTALLED

The following pictures show a sidewall flashing not properly installed, this roof is 10 years old and was new construction when installed. Manufacturer specs call for 1 step flashing per row of comp. The roof slope is only a 3/12 pitch which should have Ice & Water shield installed, best  or 2 layers of 30lb underlayment, adequate but not my first choice for low slope. Anything 3/12 below is considered low slope and certain techniques or materials must be used to insure water tight integrity.

ROOFER MADE SKYLIGHT FLASHING

Roofer made skylight flashing, not even close to the proper way of installing the upper and lower saddles. Proper saddles are bent and soldered at a sheet metal shop. Relying on sealant is no way to make something watertight and is poor practice.

TILE ROOF WITH DRY ROT

The pictures are a tile roof with dry rot at eve due to improper install. The tiles should have been an inch into the gutter and also have eve metal under the tile and over the gutter. 